PVC Insulated Copper Wire & Cable - PVC INSULATED AND PVC SHEATHED MULTI-CORE CABLES
    300/500 VOLTS
Specification

BS6004 U K Reference: 6182Y, 6183Y, 6184Y

Conductor

Plain annealed copper conductor
1.0 mm2 to 35-mm2 stranded complying with BS6360 Class 2

Insulation

PVC Insulation complying with BS 7655 requirements for TI 1
PVC Sheath complying with BS 7655 requirements for type 9

Application BIC PVC Insulated And PVC Sheathed Multi-Core Cables. 300/500 Volts are suitable for all fixed installation in dry or damp premises in walls, on boards, in channels or embedded in plaster
Core Identification (Colour)

2 Core Red or Black
3 Core Red, Yellow, Black
4 Core Black, Red, Yellow, Blue

Outer Sheath White or Grey
Temperature Limits

The cables are suitable for operation in the range of -15 to 70oC, but should not be installed in temperatures below +5oC

Packing

Up to 4 mm2 supplied on Cardboard drums of 100 yards.
Other sizes on 50/100 yard drums where applicable

 
      Two Core 6182Y Three Core 6183Y Four Core 6184Y
Range Conductor Area Number and Diameter of Wires Max. overall Diameter Cable weight per kilometer Max. overall Diameter Cable weight per kilometer Max. overall Diameter Cable weight per kilometer

mm2

No/mm

mm

Kg

mm

Kg

mm

Kg

1.5 1/1.38 10.0 138 10.5 159 11.5 192
1.5 7/0.53 10.5 138 11.0 159 12.0 192
2.5 1/1.78 11.5 177 12.0 210 13.0 252
2.5 7/0.67 12.0 177 12.5 210 13.5 252
4.0 7/0.85 13.0 238 13.5 284 15.0 361
6.0 7/1.04 14.0 304 15.5 383 17.0 486
10.0 7/1.35 17.5 428 19.0 538 20.5 694
16.0 7/1.70 20.0 580 21.5 770 23.5 970
25.0 7/2.14 24.0 860 26.0 1170 28.5 1510
35.0 19/1.53 27.5 1145 29.0 1520 32.0 1945
 
 